Product Documentation
- Brochures
- Material Safety Data Sheets
- User Guides
Specifications of these models
Dryer Model |
Inlet & Outlet |
Rated Flow at 100 psig |
Pressure Drop |
Compressor(s) |
Absorbed Power |
|||
---|---|---|---|---|---|---|---|---|
NPT(M) / Flg |
scfm |
psi |
qty |
hp |
Type |
kW |
amps |
|
3” |
1250 |
1.6 |
1 |
8 |
scroll |
10.4 |
16.4 |
|
3” |
1500 |
2.0 |
1 |
9 |
scroll |
11.8 |
17.5 |
|
3” |
1500 |
2.0 |
1 |
7.5 |
semi-hermetic |
7.5 |
14.1 |
|
4” |
1750 |
2.8 |
1 |
10 |
scroll |
13.9 |
17.8 |
|
4” |
1750 |
2.8 |
1 |
7.5 |
semi-hermetic |
7.5 |
14.1 |
|
4” |
2000 |
3.5 |
2 |
12 |
scroll |
15.1 |
18.6 |
|
6” |
2250 |
4.4 |
1 |
10 |
semi-hermetic |
10.7 |
20 |
|
6” |
2500 |
1.5 |
2 |
16 |
scroll |
15.1 |
18.6 |
|
6” |
2500 |
1.5 |
1 |
10 |
semi-hermetic |
10.7 |
20 |
|
6” |
3200 |
2.5 |
2 |
20 |
scroll |
27.7 |
35.6 |
|
8” Flg |
3200 |
2.5 |
1 |
15 |
semi-hermetic |
15.1 |
29 |
|
8” Flg |
4000 |
2.8 |
1 |
28 |
semi-hermetic |
30.5 |
45.8 |
|
8” Flg |
4000 |
2.8 |
1 |
20 |
semi-hermetic |
20.1 |
53.6 |
|
8” Flg |
5000 |
4.2 |
1 |
35 |
semi-hermetic |
38.5 |
57.5 |
|
8” Flg |
5000 |
4.2 |
1 |
30 |
semi-hermetic |
38.3 |
48.1 |
|
8” Flg |
6250 |
4.5 |
1 |
40 |
semi-hermetic |
44.4 |
65.2 |
|
8” Flg |
6250 |
4.5 |
1 |
35 |
semi-hermetic |
42.3 |
53.2 |
|
8” Flg |
7500 |
6.5 |
1 |
40 |
semi-hermetic |
37.5 |
79.3 |
Specifications |
|
---|---|
Heat exchanger type |
shell and finned tube |
Design operating pressure |
0 to 150 psig |
Design /maximum inlet air temperature range |
100°F / 120°F |
Design /maximum ambient temperature range |
100°F / 110°F |
Condenser cooling options |
air-cooled (-A) or water-cooled (-W) |
Refrigerant type |
refrigerant type R404A or R407C (dependent on model) |
Control panel enclosure |
NEMA 1 |
Power supply requirements |
460V/3Ph/60Hz |
(1) This information is for general information purposes only. For additional technical specifications, refer to the product brochure, technical data sheets, and/or user guides. Technical specifications are subject to change.